Description
- 48VDC operated. Dual AC controller with free & emergency cooling.
- AC fail alarm. Compressor fault sensing.(HP, LP).
- Over Current & Undercurrent sensing for compressor.
- Internal swapping to maintain equal run-hours.
- RS485/ RS232 connectivity(optional).
- 2 NTC for Ambient and Shelter temperature, 1 Humidity sensor.
- Digital Inputs : HP, LP, UL, OL, MCB1, MCB2.
- Digital output : Fan1, Fan2, Compressor1, Compressor2, Damper1, Damper2, Ac1 fail alarm, Ac2 fail alarm, HT alarm.
For Telecom Shelters.
- Temperature Range : 0°C to 50°C.
- Input power supply 48VDC.
- Wall Mounted.
- Note: Single AC controlling option available with wall mounting / panel mounting.